The PXK explosion proof purged panel is listed for AC220V/380V systems up to 400A. Specify the 200-600 Pa working pressure, 0.2-0.8 MPa gas source pressure, NPT3/8 gas inlet and 9-14 mm cable range with the final panel arrangement.
- AC220V/380V rated voltage
- Main circuit current up to 400A
- Working pressure 200-600 Pa
- Gas source pressure 0.2-0.8 MPa
- Gas marking Ex db eb ib pxb IIC T4 Gb
- Dust marking Ex ib mb pxb tb IIIC T130°C Db
- IP66 ingress protection and WF1 corrosion rating
- NPT3/8 gas inlet
- 9-14 mm cable diameter range
Specify the PXK Purged Panel by Pressure, Current and Cable Entry
Use the pressure and electrical values below when preparing an RFQ. Confirm the final panel arrangement and project approval requirements before release.
| Parameter | Specification |
|---|---|
| Model / Series | PXK IIC |
| Rated Voltage | AC 220V / 380V |
| Main Circuit Current | ≤ 400A |
| Working Pressure | 200-600 Pa |
| Gas Source Pressure | 0.2-0.8 MPa |
| Gas Protection Marking | Ex db eb ib pxb IIC T4 Gb |
| Dust Protection Marking | Ex ib mb pxb tb IIIC T130°C Db |
| Ingress Protection | IP66 |
| Corrosion Rating | WF1 |
| Gas Inlet | NPT3/8 |
| Cable Diameter | 9-14 mm |